Measurement range temp.:
|
0...+50°C |
Measurement range VOC:
|
0-100% (good / bad air quality, referring to the calibration gas) |
Accuracy:
|
±15% FS |
Long term stability:
|
< 15% FS/year at norm load |
Sensor:
|
VOC: metal oxide sensor, Temperature: resistance sensor |
Response time (t90):
|
max. 60 s |
Sensor protection:
|
screwable stainless steel sinter filter |
Supply voltage:
|
24 V AC/DC (±5%) |
Current consumption:
|
max. 60 mA |
Analogue output 0-10 V:
|
3-wire connection, min. load resistance 100 kOhm |
Alarm output:
|
1 x potential-free change-over contact, 48 V, 1 A |
Switching Hysteresis Relay:
|
2% FS (without Display), 0,5...5% FS adjustable (with Display) |
Electrical connection:
|
screw terminals max. 1,5 mm² |
Display:
|
optional LCD display with backlight on/off/auto |
Automatic calibration:
|
The automatic VOC calibration takes place every 7 days, this compensates for any drifts and achieves excellent long-term stability. To ensure this function, the device must be supplied with power for at least 7 days without interruption and ventilated with fresh air once for approx. 10 minutes within this period.
The automatic calibration can be deactivated if necessary and performed manually. |
Running-in time:
|
1 h |
Initial operation:
|
After switch-on of the device follows a self-test and the tempering, which takes ca. 1 h depending on the environmental conditions. At this time the analogue output drifts from the actual measurement value. |
Material:
|
Protection tube: metal |
Cable gland:
|
PG11 high-strength cable gland with strain relief |
Housing:
|
Polycarbonate PC UL 94 V0 with hinge locks, color signal white similar to RAL 9003 |
Dimensions:
|
Housing: L 89 x W 80 x H 47 mm, Protection tube: Ø 16 x 190 mm |
Weight:
|
250 g |
Protection type:
|
Housing/electronic: IP65, Sensor: IP30 |
Protection class:
|
III |
Working range r.H.:
|
0...98% r.H. in contaminant-free, non-condensing air |
Working temperature:
|
0...+50°C |
Manual calibration:
|
The manual VOC calibration of the output signal to 1V (zero point) is started by pressing the button on the circuit board (hold down for approx. 5 seconds until the LED flashes). Before that, continuous operation of min. 2 hours with air defined as normal air quality. The LED is deactivated after successful calibration. |
Storage temperature:
|
-20...+50°C |
Installation:
|
mounting flange (in scope of delivery) |
Approvals:
|
CE, EAC, RoHS |